ASTM D93 - 02
Standard Test Methods for Flash-Point by Pensky-Martens Closed Cup Tester
| Aviso: | Las normas ASTM en lectura se visualizan a través del área decliente. Los archivos no se pueden descargar |
|---|---|
| Fecha edición: |
2002-06-10
Anulada
|
| Fecha cancelación: | 2002-06-10 |
| Idiomas disponibles: | Inglés |
| Resumen: | |
| Keywords: | automated flash point; automated Pensky-Martens closed cup; flammability; flash point; Pensky-Martens closed cup |
| Scope: | 1.1 This test method covers the determination of the flash point of petroleum products in the temperature range from 40 to 360oC by a manual Pensky-Martens closed-cup apparatus or an automated Pensky-Martens closed-cup apparatus. Note 1—Flash point determination as above 250oC can be performed, however, the precisions have not been determined above this temperature. For residual fuels, precisions have not been determined for flash points above 100oC. 1.2 Procedure A is applicable to distillate fuels (diesel, kerosene, heating oil, turbine fuels), new lubricating oils, and other homogeneous petroleum liquids not included in the scope of Procedure B. 1.3 Procedure B is applicable to residual fuel oils, cutback residua, used lubricating oils, mixtures of petroleum liquids with solids, petroleum liquids that tend to form a surface film under test conditions, or are petroleum liquids of such kinematic viscosity that they are not uniformly heated under the stirring and heating conditions of Procedure A. Note 2--Liquids having kinematic viscosities less than 5.5 mm 2/s (cSt) at 40oC (104oF), do not contain suspended solids, or do not have a tendency to form a surface film while under test conditions, can be tested in accordance with Test Method D56. 1.4 This test method is applicable for the detection of contamination of relatively nonvolatile or nonflammable materials with volatile or flammable materials. 1.5 The values stated in SI units shall be regarded as the standard. The values given in parentheses are provided for information only. 1.6 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. For specific hazards statements, see 6.4, 7.1, 9.3, 9.4, 11.1.2, 11.1.4, and 12.1.2 |
| ICS: | 75.080 - Productos petrolíferos en general, 75.160.20 - Combustibles líquidos, 13.220.40 - Comportamiento frente al fuego e inflamabilidad de materiales y productos |
| CTN: | D02.08 - D02.08 |
|
Otras Relaciones |
Es referenciada por D3278-21 Es referenciada por D5146-10R19 Es referenciada por E0709-21 Es referenciada por D5966-22 Es referenciada por D6217-21 Es referenciada por D8324-21 Es referenciada por D7960-21 Es referenciada por F1201-88R21 Es referenciada por F1200-21A Es referenciada por C0916-20 Es referenciada por D3941-20 Es referenciada por D8175-18 Es referenciada por E0502-21A Es referenciada por D7666-12R19 Es referenciada por D0333-01R21 Es referenciada por D3955-20 Es referenciada por D6468-22 Es referenciada por D3934-20 Es referenciada por D4625-21 Es referenciada por D5967-21 |